» Project Specifications: Buildings > 75' Copper Equipment
GENERAL:
Provide a complete Lightning Protection System as shown on the drawings and as specified herein. This system shall
be installed by a firm actively engaged in the installation of Master Labeled Lightning Protection Systems a minimum of
five (5) years and shall be listed by Underwriters Laboratories, such as Maxwell Lightning Protection Company, 621 Pond
Street, Dayton, Ohio 45402, (937) 228-7250, or 1-800-872-1657.
The completed system shall comply with the latest edition of the Installation Requirements for Master Labeled Lightning Protection System U.L. 96A, and the National Fire Protection Association must be L.P.I. certified and in good standing and so certified.
MATERIALS:
All materials used in this installation shall be labeled or listed by Underwriters Laboratories, Inc. for use in Master
Labeled Lightning Protection Systems. The catalog numbers referred to on the drawings and herein are those of EAST COAST
LIGHTNING PROTECTION, MAXWELL LIGHTNING PROTECTION COMPANY or THOMPSON LIGHTNING PROTECTION.
AIR TERMINALS:
Air terminals shall project a minimum of ten (10) inches above the objects protected and shall be located at intervals not
exceeding 20' 0" along ridges and around the perimeter of flat roof or gently sloping roofs. Flat or gently sloping roofs
exceeding 50' 0" in width shall be provided with additional air terminals at intervals not exceeding 50' 0" on the flat or
gently sloping area. Air terminals shall be located within 24 inches of the roof edge and outside corners of the protected
area.
Air terminals shall be provided for metal stacks, flues and mechanical equipment having a metal thickness of less than 3/16" and not within a zone of protection of an air terminal. Equipment with metal thickness 3/16" or greater shall be bonded per code requirements.
Air terminals shall be No. 71, 1/2" X 12" (or longer as required) solid copper using air terminal bases of cast bronze construction.
CONDUCTORS:
Main size conductors on the roof shall be No. 28, Class II copper lightning conductor consisting of 28 strands of 14 AWG
copper wire weighing 375 lbs. per 1000 feet.
All secondary bonding conductors shall be No. 14, secondary bonding conductor consisting of 14 strands of 17 AWG copper wire.
All down conductors shall be No. 28, Class II copper lightning conductor. Down conductors shall be concealed in exterior wall construction.
Note: Buildings over 60' require a conductor counterpoise cable of 28/14 copper to meet N.F.P.A. code requirements for this project.
ROOF PENETRATION - FOR NEW CONSTRUCTION:
All roof penetrations shall be made using a conduit sleeve passing through a No. 227G pitch pocket. The pitch pocket shall
be installed by the roofing contractor. The roofing contractor must include all additional expenses for this additional
work. Any roof pads, or roof stripping must be supplied and installed by the roofing contractor, at the roofing contractors
expense, to maintain the roof warranty.
COMMON GROUNDING AND BONDING OF METAL BODIES:
Common grounding of all mediums within the building shall be ensured by connection to cold water piping or by direct
bonding using main size conductors and fittings.
Metal bodies of conductance (metal bodies with a metal thickness of 3/16" or greater and not located within the zone of protection of an air terminal) shall be bonded using main size conductors and fittings per code requirements.
Metal bodies of inductance (metal bodies located within 6' 0" of the lightning protection system) shall be bonded to the system using secondary bonding conductors and fittings unless inherently bonded through construction to another bonded metal body.
GROUND ELECTRODES:
Ground electrodes shall be No. 5810, 5/8" X 10' long copper clad ground rods located as shown on the drawings. Down
conductors shall be connected to the ground rods using exothermic weld connections.
STRUCTURAL STEEL SYSTEM:
Structural steel may be substituted for down conductors. Ground main steel columns and average of 60' using Class II
material. Roof penetrations from steel to perimeter cables at 100', per U.L. 96A, L.P.I. 175, and N.F.P.A. 780. Use
exothermic weld to all steel connections.
INSPECTION AND ACCEPTANCE:
Upon completion of the installation the contractor shall deliver to the owner the Master Label issued by Underwriters
Laboratories, Inc. for this system. If the new addition connects to an existing building that is not protected or
brought up-to-date a U.L. Letter of Findings must be obtained, at the lightning protection contractors expense.
Note: Surge Arresters at the main electrical panel are not included under our scope of work. This item must be installed and supplied by the Electrical Contractor.
SUBMITTALS:
Drawings shall be submitted for approval before delivering material and beginning work. Drawings to show number of
points, size locations, conductor routes and size, grounding and details of connectors. Catalog data for all items or
material used shall be submitted.
Lightning protection contractor shall submit his Underwriters Laboratories listing number, along with a copy of ten successful U.L. inspection certificates and their identification numbers installed in the last five years. Contractor must show proof of insurance and must be substance to be bonded.
quick contact form
Before hiring an lightning protection company, verify that the installer is UL Listed. Call the Follow-Up
Services department at UL's office:
333 Pfingsten Road
Northbrook, IL 60062
(847) 272-8800